Decarbonization is an urgent challenge, so we need to understand the levers that will have the most impact, most quickly. LCAs are essential because they allow us to evaluate the whole footprint of a product or system (and not just carbon but a range of environmental impacts), pinpoint the most effective reduction strategies, and avoid shifting impacts from one life cycle stage to another. They’re invaluable at design stage because they enable sustainability to be factored into decisions alongside feasibility and cost analysis.
Microsoft intends to apply the insights from this research to optimize the cooling design of future data centers, supporting its broader sustainability goals. WSP’s purpose is to shape communities to advance humanity, so I’m really pleased that the paper is also accompanied by a free, open-source, Excel-based tool that any data center operator or designer can use to evaluate different server cooling technologies and locations and consider the trade-offs between them. It can also help purchasers of cloud services or data center capacity to understand the emissions or water implications in the context of their own sustainability targets. WSP works with organizations in many sectors to quantify their direct and indirect impacts, and to develop strategies to mitigate them, and we can help apply this tool to different contexts.
Headline findings
We looked at three technologies – cold plate, one-phase immersion and two-phase immersion – comparing them against traditional air-cooling. Each has pros and cons, but it has been assumed that their benefits outweigh the drawbacks. We set out to quantify the environmental impacts to inform better decisions.
Our research found that using liquid cooling in data centers could reduce greenhouse gas emissions by 15-21%, energy demand by 15-20%, and blue water (freshwater) consumption by 31-52%. For a typical hyperscale facility, these reductions could be broadly equivalent to removing up to 4,500 cars from US roads annually, powering around 22,200 US homes, or saving approximately 20 Olympic swimming pools of water. These figures are illustrative and based on specific assumptions outlined in the study.
When we’re producing LCAs for complex systems, one of the first challenges is to identify a single unit for comparing systems that perform similar functions in different ways. Here, we chose the annualized virtual core (Vcore) as our “functional unit”. This is the basic unit of the cloud, representing the amount of computing power used over a year, and it enables comparison of different data center configurations and locations across the entire ecosystem.
The graph below summarizes our findings: it shows the GHG emissions, total energy demand and blue water consumption impacts for each technology, per Vcore per year.
We modeled two different power sources for the operation of the data center: one with 0% renewable energy as a baseline (representing a fossil-based grid), and one with 100% renewable energy (reflecting Microsoft’s commitment to renewable energy). All of the results are shown relative to the impact of an air-cooled data center powered by 0% renewable energy.